Skip to main content

Heating Loads for the Flatrock Passive House

In the previous post, I presented some numbers from the modelling of my passive house.  Although, the loads showed, a maximum of 3.8 kW, that didn't include the thermal gains or the solar gains so infact, the total load will be significantly less.  

The PHPP software can only provide static numbers for a whole house and doesn't do any type of room-by-room analysis for heat loads.  The PHPP software showed that the total load would be 2.8 kW once internal gains are taken into account.  However, in order to ensure heating is distributed uniformly, a more conventional engineering heat load calculation program is used.  The table below shows the heat loads required to maintain 20 C inside when its -18 C outside:


Look closely...the numbers are tiny!  The upstairs hallway requires 22 W!, The main bath requires 83 W!  Even running a 100 W light bulb in that room will be sufficient!   However a light bulb is not considered a heat source so we need to explore options for heat sources, a way to distribute the heat and whether or not a couple of zones in the house along with natural air movement is enough to move heat from those zone sources around the home.

The largest heat load is in the kitchen/dining room.  At 700 W, this gives, 18.6 W/sq. m.!  In the master ensuite, we will require 155 W or 13.8 W/sq. m.  These numbers are so small that finding heaters are almost impossible.  Where will you find a 100W baseboard?  You won't.  This is typically why these homes use point source heat rather than huge distribution systems like ducts.   Point source heaters, a few in select areas, along with natural stratification is usually enough to distribute heat as long as the HRV/ERV is circulating air.

The average human body radiates 100 W of thermal energy while resting.   So two adults sleeping in the master bedroom on the coldest day of the year will heat a room like a 200 W heater.  The difference according the load table is about 49.4 W.  Unfortunately, sleeping with a light bulb on is not an option.  But if it were, it would make a great heat source!  It is very unlikely that heating will even be required on most winter nights in the rooms unless the temperature outside is less than -5 C.  A body in the rooms will almost be enough to keep it comfortable!

Next step:  Determine how to heat the space....Lots of ideas for my next post!







Comments

Popular posts from this blog

Building the Air Tight Barrier: Door Flashing Details.

It took us a while to wrap our heads around the door details on my plans.  The main exterior wall is composed of 2x8s.  The rough stud opening was substantially larger than the door.  Because the walls are much deeper than a standard door frame for a 2x6 wall, the interior of the 2x8 opening was studded with double 2x4s.   Outside of these 2x4s, there is 1.5" of foam and another 2x4 on face which brings the door frame opening flush to the exterior 3" of EPS foam.  The brick mould of the door will sit against the exterior of the wall.  The ganged 2x4s which define the opening will allow the door to open a little further than that of a 2x8 wall.    With the door details finalized, I had to flash the opening as per the plan.  I specified the size/shape for aluminum sill pans and CBS Eavestroughing made them for me.  The sill pans have a kind of end dam to prevent water from entering under the under the stud opening should the door ever leak. (Photo 1-1).   After verifying t

Choosing an HRV...My Thoughts....

So, which HRV do you want for your home?  This is a question not often asked by the homeowner.  When the house is built, somebody installed an HRV and that was it.  The home owner is rarely involved in anything other than turning a knob on the HRV wall control if they dare fool with it at all.  An HRV is probably one of the most important appliances in your house;  it expels moisture, eliminates odours, evacuates stale air from bathrooms, provides clean air to keep you healthy and it recovers a lot of heat that would have otherwise been blown out through the vent on the house.  It serves three main functions: 1.  Supplies the home with fresh dry air. 2.  Removes stale air and removes excess moisture. 3.  Recovers heat or heat/moisture For a low energy home we need an HRV that is as efficient as possible.  With the ventilation unit taking care of exchanging most of the air in the building, having an efficient one will pay for itself in the energy saved over it's lifetime.  Zeh

Introducing: The Flatrock Passive House

So...after 8 1/2 years in our home, we have decided to move on.  Well, not right away! We have quite a bit of planning ahead of us.  With the likely onset of a 233% hike in the cost of electricity from Muskrat Falls (when compared to todays rate of $0.0972/kWh) we decided it was time to take energy consumption seriously before its too late to do anything about it.  The land has been acquired, the planning has started!  I am planning on nipping my energy bill in the bud before it becomes a major sinkhole in my pocket book. Upon investigating current building standards, I realized that the Canadian Building Code is below the standards necessary to really make a difference in energy consumption.  There are some standards like R2000 which can make a difference to total energy usage.  A R-2000 home can use up to 50% less heating energy compared to a code built home; if built properly!  A blower door test will reveal the truth about that. Now....Imagine living in a home where you have em